HVAC SYSTEM (HEATER, VENTILATOR AND A/C) > Pressure Switch (Triple Pressure Switch)
INSPECTION
1. Connect the manifold gauge to the service valve on the high-pressure side.
2. Disconnect the connector.
3. Start the air conditioner, and check the operating pressure of switch by turning the compressor assembly (magnet clutch) to ON/OFF. Operation of each switch is as follows.

(1) | High pressure switch | (6) | 1,770±100 kPa (18.05±1.02 kg/cm2, 256.65±14.5 psi) | (11) | OFF |
(2) | Middle pressure switch | (7) | 1,470±120 kPa (14.99±1.22 kg/cm2, 213.15±17.4 psi) | (12) | Operative range of compressor ASSY |
(3) | Low pressure switch | (8) | 225±30 kPa (2.29±0.31 kg/cm2, 32.6±4.3 psi) | (13) | Inoperative range of compressor ASSY |
(4) | 2,350±200 kPa (24.00±2.04 kg/cm2, 340.7±29.0 psi) | (9) | 196±25 kPa (2.00±0.25 kg/cm2, 28.4±3.6 psi) | (14) | Low pressure |
(5) | 2,940±200 kPa (29.98±2.04 kg/cm2, 426.3±29.0 psi) | (10) | ON | (15) | High pressure |
NOTE:
• High pressure switch turns the compressor assembly (magnet clutch) to OFF when the refrigerant pressure becomes extremely high to prevent the evaporator, air conditioner piping and expansion valve from getting damaged or frozen, etc.
• The middle pressure switch is used to effectively control the radiator fan output by judging high load/low load in normal pressure range.
• The low pressure switch detects a refrigerant shortage and deactivates the compressor assembly (magnet clutch) if the refrigerant pressure is abnormally low. (Because any further compressor assembly operation in such a state may lead to compressor seizure)
Diagnostics with phenomenon Inspection
Refrigerant charging procedure ProcedureDtc u0073 control module communication bus off
INSTRUMENTATION/DRIVER INFO (DIAGNOSTICS) > Diagnostic Procedure with Diagnostic Trouble Code (DTC)DTC U0073 CONTROL MODULE COMMUNICATION BUS OFFDetected when CAN line abnormality is detected.NOTE:Perform the diagnosis for LAN system. Basic Diagnostic Procedure > PROCEDURE"> ...
Disassembly
COOLING(H4DO) > Radiator Sub Fan and Fan MotorDISASSEMBLY1. Remove the clip which holds the sub fan motor connector onto the radiator sub fan shroud.2. Disconnect the radiator sub fan from the sub fan motor.3. Disconnect the sub fan motor from the radiator sub fan shroud. ...
Interior light off delay timer setting
1. Perform the preparation steps according
to "Preparation for car settings"
2. Operate the " " or "
" switch to
select the "Interior Light" item. Then push
the button.
3. The current setting will be displayed.
Push the button to enter the
selection
mode.
4. Select ...